Option
Name
Description
[0]
None
[1]
10 Mbps
[2]
100 Mbps
Parameter 12-14 Link Duplex
Table 617: Parameter 12-14 Link Duplex
12-14 Link Duplex
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
N O T I C E
In POWERLINK, this parameter is locked to half duplex.
Forces the duplex for each port to full or half duplex. If
parameter 12-12 Auto Negotiation
is set to
[1] On
, this parameter is read-only.
Option
Name
Description
[0]
Half duplex
[1]
Full duplex
Parameter 12-18 Supervisor MAC
Table 618: Parameter 12-18 Supervisor MAC
12-18 Supervisor MAC
Default value: 0
Parameter type: Range, 0 - 2147483647
Setup: All setups
Conversion index: 0
Data type: OctetString
Change during operation: True
MAC addresses of currently active supervisors.
Parameter 12-19 Supervisor IP Addr.
Table 619: Parameter 12-19 Supervisor IP Addr.
12-19 Supervisor IP Addr.
Default value: 0
Parameter type: Range, 0 - 2147483647
Setup: All setups
Conversion index: 0
Data type: OctetString
Change during operation: True
IP addresses of currently active supervisors.
5.12.3 12-2* Process Data
Parameter 12-20 Control Instance
Table 620: Parameter 12-20 Control Instance
12-20 Control Instance
Default value: Size related
Parameter type: Range, 0 - 255
Setup: 1 setup
Conversion index: 0
Data type: Uint8
Change during operation: True
This parameter is read-only. It shows the connection to the master.
AU275636650261en-000101 / 130R0334 | 351
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide