Parameter 6-35 Term. X30/11 High Ref./Feedb. Value
Table 417: Parameter 6-35 Term. X30/11 High Ref./Feedb. Value
6-35 Term. X30/11 High Ref./Feedb. Value
Default value: Size related Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Sets the analog input scaling value to correspond to the high-voltage value (set in
parameter 6-31 Terminal X30/11 High Voltage
).
Parameter 6-36 Term. X30/11 Filter Time Constant
Table 418: Parameter 6-36 Term. X30/11 Filter Time Constant
6-36 Term. X30/11 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: -3
Data type: Uint16
Change during operation: True
N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X30/11. Increasing the value improves dampening but also increases the time delay through the filter.
5.7.5 6-4* Analog Input X30/12
Parameter group for configuring the scale and limits for analog input 4 (X30/12) in VLT® General Purpose I/O MCB 101.
Parameter 6-40 Terminal X30/12 Low Voltage
Table 419: Parameter 6-40 Terminal X30/12 Low Voltage
6-40 Terminal X30/12 Low Voltage
Default value: Size related
Parameter type: Range, -10.00 - par. 6-41 V
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Sets the analog input scaling value to correspond to the low reference feedback value set in
parameter 6-44 Term. X30/12 Low Ref./
Feedb. Value
.
Parameter 6-41 Terminal X30/12 High Voltage
Table 420: Parameter 6-41 Terminal X30/12 High Voltage
6-41 Terminal X30/12 High Voltage
Default value: 10 V
Parameter type: Range, par. 6-40 V - 10 V
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Sets the analog input scaling value to correspond to the high reference feedback value set in
parameter 6-45 Term. X30/12 High Ref./
Feedb. Value
.
AU275636650261en-000101 / 130R0334 | 237
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide