Op-
tion
Name
Description
(X
h
) on induction motors. Ensure that the motor poles specified in
parameter 1-39 Motor Poles
are correct
for accurate back EMF measurement.
[6]
Enable 360°
turn OL
Sensorless:
Performs a 360 degree test run in sensorless mode to verify the number of motor poles speci-
fied in
parameter 1-39 Motor Poles
.
Closed loop:
Performs a 360 degree test run in sensorless mode to test the encoder before running in
closed loop. The speed is set in
parameter 3-19 Jog Speed [RPM]
. During the test run, the direction of rota-
tion is verified and the number of pulses per revolution is verified to match the configuration in
parameter
group 17-** Motor Feedb. Option
or
parameter group 5-** Digital In/Out
based on the selected encoder.
After completing the 360 degree test run, either of the following messages are shown:
Encoder/Resolver OK
Encoder/Resolver Fail
Encoder/Resolver Inverted
Encoder/Resolver resolution/poles low
Encoder/Resolver resolution/poles high
The
parameter 1-41 Motor Angle Offset
is automatically set when using PM motor and absolute encoder or
resolver.
[7]
Enable in-
ertia run
Use this option to ramp up in the mode as specified in
parameter 1-01 Motor Control Principle
. Measured
inertia is set in
parameter 1-69 System Inertia
and
parameter 7-08 Speed PID Feed Forward Factor
is set to
90%.
N O T I C E
For the best adaptation of the drive, run AMA on a cold motor.
AMA cannot be performed while the motor is running
AMA cannot run with a sine-wave filter connected.
N O T I C E
It is important to set
parameter group 1-2* Motor Data
correctly, since these form part of the AMA algorithm. Perform an AMA to
achieve optimum dynamic motor performance. It may take up to 10 minutes, depending on the power rating of the motor.
N O T I C E
Avoid generating external torque during AMA.
N O T I C E
If 1 of the settings in
parameter 1-2* Motor Data
is changed,
parameter 1-30 Stator Resistance (Rs)
to
parameter 1-39 Motor Poles
return to default setting.
N O T I C E
AMA works problem-free on 1 motor size down, typically works on 2 motor sizes down, rarely works on 3 sizes down, and never
works on 4 sizes down. Keep in mind that the accuracy of the measured motor data is poorer when operating on motors smaller
than the nominal drive size.