Parameter 32-07 Absolute Encoder Clock Generation
Table 1118: Parameter 32-07 Absolute Encoder Clock Generation
32-07 Absolute Encoder Clock Generation
Default value: [1] On
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data trype: Uint8
Change during operation: True
Option Name Description
[0]
Off
Select
[0] Off
when more MCOs are connected to the same absolute encoder. Only 1 MCO is allowed to gener-
ate the clock signal when multiple MCOs are interconnected.
[1]*
On
Select
[1] On
when 1 MCO is connected to 1 absolute encoder.
Parameter 32-08 Absolute Encoder Cable Length
Table 1119: Parameter 32-08 Absolute Encoder Cable Length
32-08 Absolute Encoder Cable Length
Default value: 0
Parameter type: Range, 0 - 300 m
Setup: 2 setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Set the total cable length (in meters) to avoid that the absolute encoder (SSI) signals come out of synchronization due to signal
delays caused by long encoder cables. VLT® Motion Control Option MCO 305 and VLT® Motion Control Option MCO 302 compen-
sate for the cable delay when the cable length is known.
Parameter 32-09 Encoder Monitoring
Table 1120: Parameter 32-09 Encoder Monitoring
32-09 Encoder Monitoring
Default value: [0] Off
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Off
[1]
3 channels
[2]
2 channels
[3]
Warning
[4]
Alarm
Parameter 32-10 Rotational Direction
Table 1121: Parameter 32-10 Rotational Direction
32-10 Rotational Direction
Default value: [1] No action
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
Normally, a positive reference value brings about a positive change of the position. If this is not the case, the reference value can be
reversed internally.