N O T I C E
Run an AMA to set the value of this parameter. Edit the value manually only when the application requires a value other than
determined by AMA.
Enter the q-axis inductance saturation point. The drive uses this value to optimize the performance of IPM motors. Select the value
that matches the point where the inductance equals the average value of
parameter 1-38 q-axis Inductance (Lq)
and
parameter 1-45
q-axis Inductance Sat. (LqSat)
, as a percentage of nominal current.
5.2.6 1-5* Load Indep. Setting
N O T I C E
The following parameter is only available in FC 302:
Parameter 1-53 Model Shift Frequency
This parameter group contains parameters related to:
Motor nameplate load compensations.
Application load type.
Electronic brake function for quick stop/hold of the motor.
Parameter 1-50 Motor Magnetization at Zero Speed
Table 101: Parameter 1-50 Motor Magnetization at Zero Speed
1-50 Motor Magnetization at Zero Speed
Default value: 100%
Parameter type: Range, 0 - 300%
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
N O T I C E
Parameter 1-50 Motor Magnetisation at Zero Speed
has no effect when
parameter 1-10 Motor Construction
=
[1] PM, nonsalient SPM
.
Use this parameter along with
parameter 1-51 Min Speed Normal Magnetising [RPM]
to obtain a different thermal load on the motor
when running at low speed. Enter a value which is a percentage of the rated magnetizing current. If the setting is too low, the
torque on the motor shaft may be reduced.
Magn. current
e
3
0
b
a
0
4
5
.1
2
Hz
Par.1-50
Par.1-51
100%
Par.1-52
RPM
Illustration 33: Motor Magnetization
Parameter 1-51 Min Speed Normal Magnetising [RPM]
Table 102: Parameter 1-51 Min Speed Normal Magnetising [RPM]
1-51 Min Speed Normal Magnetising [RPM]
Default value: Size related
Parameter type: Range, 10 - 600 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
AU275636650261en-000101 / 130R0334
88 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide