Option
Name
Description
[4]
Bus: No access
No access to parameters is allowed via fieldbus and/or FC standard bus.
[5]
All: Read only
Read-only function for parameters on LCP, fieldbus, or FC standard bus.
[6]
All: No access
No access from LCP, fieldbus, or FC standard bus is allowed.
If
[0] Full access
is selected,
parameter 0-60 Main Menu Password
,
parameter 0-65 Personal Menu Password
, and
parameter 0-66 Access
to Personal Menu w/o Password
are ignored.
N O T I C E
A more complex password protection is available for OEMs upon request.
Parameter 0-65 Personal Menu Password
Table 38: Parameter 0-65 Personal Menu Password
0-65 Personal Menu Password
Default value: 200
Parameter type: Range, -9999 - 9999
Setup: 1 setup
Conversion index: 0
Data type: Int16
Change during operation: True
Define the password for access to the Quick Menu via the [Quick Menu] key. If
parameter 0-66 Access to Personal Menu w/o Password
is set to
[0] Full access
, this parameter is ignored.
Parameter 0-66 Access to Personal Menu w/o Password
Table 39: Parameter 0-66 Access to Personal Menu w/o Password
0-66 Access to Personal Menu w/o Password
Default value: [0] Full access
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
If
parameter 0-61 Access to Main Menu w/o Password
is set to
[0] Full access
, then this parameter is ignored.
Option
Name
Description
[0]*
Full access
Disables password defined in
parameter 0-65 Personal Menu Password
.
[1]
LCP: Read only
Prevent unauthorized editing of Quick Menu parameters.
[3]
Bus: Read only
Read-only functions for Quick Menu parameters on fieldbus and/or FC standard bus.
[5]
All: Read only
Read-only function for Quick Menu parameters on LCP, fieldbus, or FC standard bus.
Parameter 0-67 Bus Password Access
Table 40: Parameter 0-67 Bus Password Access
0-67 Bus Password Access
Default value: 0
Parameter type: Range, 0 - 9999
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Use this parameter to unlock the drive via fieldbus or VLT® Motion Control Tool MCT 10.