5.9.2 8-1* Ctrl. Word Settings
Parameter 8-10 Control Word Profile
Table 503: Parameter 8-10 Control Word Profile
8-10 Control Word Profile
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the
fieldbus installed in slot A are visible in the LCP display. For guidelines in selection of
[0] FC profile
and
[1] PROFIdrive profile
, refer to
the product-specific design guide. For more guidelines in the selection of
[1] PROFIdrive profile
, refer to the Installation Guide for the
installed fieldbus.
Option Name
Description
[0]
FC profile
[1]
PROFIdrive profile
[3]
FC motion profile
N O T I C E
This option is only available with software version 48.XX.
Assigns motion-specific functions to various control and status word bits. This option is available
when
[9] Positioning
or
[10] Synchronization
is selected in
parameter 1-00 Configuration Mode
.
[5]
ODVA
[7]
CANopen DSP 402
[8]
MCO
Parameter 8-13 Configurable Status Word STW
Table 504: Parameter 8-13 Configurable Status Word STW
8-13 Configurable Status Word STW
Default value: Size related
Parameter type: Option, Array [16]
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the
fieldbus installed in slot A are visible in the LCP display. For more guidelines in the selection of
[1] PROFIdrive profile
, refer to the
Installation Guide for the installed fieldbus.
Option Name
Description
[0]
No function
The input is always low.
[1]
Profile default
Dependent on the profile set in
parameter 8-10 Control Profile
.
[2]
Alarm 68 Only
The input goes high whenever
Alarm 68 Safe Stop Activated
is active and goes low
whenever
Alarm 68 Safe Stop Activated
is not activated.
[3]
Trip excl Alarm 68
AU275636650261en-000101 / 130R0334 | 275