5.9.8 8-9* Bus Jog
Parameter 8-90 Bus Jog 1 Speed
Table 540: Parameter 8-90 Bus Jog 1 Speed
8-90 Bus Jog 1 Speed
Default value: Size related
Parameter type: Range, 0 - Par. 4-13 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Enter the jog speed. Activate this fixed jog speed via the serial port or fieldbus option.
Parameter 8-91 Bus Jog 2 Speed
Table 541: Parameter 8-91 Bus Jog 2 Speed
8-91 Bus Jog 2 Speed
Default value: Size related
Parameter type: Range, 0 - Par. 4-13 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Enter the jog speed. Activate this fixed jog speed via the serial port or fieldbus option.
5.10 Parameter Group 9-** PROFIBUS
Parameter 9-00 Setpoint
Table 542: Parameter 9-00 Setpoint
9-00 Setpoint
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation:
This parameter receives cyclic references from a master class 2. If the control priority is set to master class 2, the reference for the
drive is taken from this parameter, whereas the cyclic reference is ignored.
Parameter 9-07 Actual Value
Table 543: Parameter 9-07 Actual Value
9-07 Actual Value
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation:
This parameter delivers the MAV for a master class 2. The parameter is valid if the control priority is set to master class 2.
Parameter 9-15 PCD Write Configuration
Table 544: Parameter 9-15 PCD Write Configuration
9-15 PCD Write Configuration
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint16
Change during operation: True
Select the parameters to be assigned to PCD 3–10 of the telegrams. The number of available PCDs depends on the telegram type.
Values in PCD 3–10 are written to the selected parameters as data. For standard PROFIBUS telegrams, see
parameter 9-22 Telegram
Selection
.