Option Name
Description
[78]
Logic rule 8
See
parameter group 13-4* Logic Rules
. If logic rule 8 in SLC is true, the output goes high. Oth-
erwise, it is low.
[79]
Logic rule 9
See
parameter group 13-4* Logic Rules
. If logic rule 9 in SLC is true, the output goes high. Oth-
erwise, it is low.
[80]
SL digital output A
See
parameter 13-52 SL Controller Action
. Output A is low on smart logic action
[32] Set digital
out A low
. Output A is high on smart logic action
[38]
.
[81]
SL digital output B
See
parameter 13-52 SL Controller Action
. Output B is low on smart logic action
[33] Set digital
out B low
. Output B is high on smart logic action
[39]
.
[82]
SL digital output C
See
parameter 13-52 SL Controller Action
. Output C is low on smart logic action
[34] Set digital
out C low
. Output C is high on smart logic action
[40]
.
[83]
SL digital output D
See
parameter 13-52 SL Controller 1 Action
. Output D is low on smart logic action
[35] Set digi-
tal out D low
. Output D is high on smart logic action
[41]
.
[84]
SL digital output E
See
parameter 13-52 SL Controller Action
. Output E is low on smart logic action
[36] Set digital
out E low
. Output E is high on smart logic action
[42]
.
[85]
SL digital output F
See
parameter 13-52 SL Controller Action
. Output F is low on smart logic action
[37] Set digital
out F low
. Output F is high on smart logic action
[43]
.
[90]
kWh counter pulse
[96]
Reverse after ramp
N O T I C E
This option is only available with software version 48.XX.
See the description in
parameter group 5-3* Digital Outputs
.
[98]
Virtual master dir.
N O T I C E
This option is only available with software version 48.XX.
See the description in
parameter group 5-3* Digital Outputs
.
[120]
Local ref active
Output is high when
parameter 3-13 Reference Site
=
[2] Local
or when
parameter 3-13 Refer-
ence Site
=
[0] Linked
to hand auto at the same time as the LCP is in hand-on mode.
Table 361: Local Reference Active
Reference site set in
parameter 3-1 3 Reference Site
Local reference active [120]
Remote reference active [121]
Reference site: Local
parameter 3-13 Reference Site [2] Local
1
0
Reference site: Remote
parameter 3-13 Reference Site [1] Remote
0
1
Reference site: Linked to Hand/ Auto
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
AU275636650261en-000101 / 130R0334 | 213
Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide