Option
Function
[128] Dir. home sen.
inv.
N O T I C E
This option is only available with software version 48.XX.
Normally closed contact for defining the home position at the same edge of the sensor signal inde-
pendent of running direction. Only for the 2 homing types
[2] Home Sync
and
[9] Direction with Sensor
.
[190] Emcy mode ref
bit 0
Enables a choice between 1 of the 8 preset reference according to
.
[191] Emcy mode ref
bit 1
Enables a choice between 1 of the 8 preset reference according to
.
[192] Emcy mode ref
bit 2
Enables a choice between 1 of the 8 preset reference according to
.
[193] Emcy mode
setup bit 0
Switch between emergency mode setup 1 to 4 in
parameter group 24-0* Emergency Mode
and
parame-
ter group 24-4* Emergency Mode 2
without changing starting setup mode for the rest of the parameters.
[194] Emcy mode
setup bit 1
Switch between emergency mode setup 1 to 4 in
parameter group 24-0* Emergency Mode
and
parame-
ter group 24-4* Emergency Mode 2
without changing starting setup mode for the rest of the parameters.
[195] Test emcy
mode
Activation of emergency mode via
parameter 24-09 Emergency Mode Alarm Handling
, option
[2] Trip all
alarms/test
with stop on all alarms and in normal operation mode. The test timer is set in
parameter
24-42 Timeout for Emergency Mode Test
, and countdown starts when the test signal is active.
[196] Reset emcy
mode
When operating in emergency mode with impulse signals (
parameter 24-43 Emergency Mode Signal Op-
eration
, option
[2] Impulse, set-reset
) the reset signal stops the emergency mode operation.
[231] Power limit
mot.
N O T I C E
This option is only available in FC 302.
Serves as input to activate the power limit function in the motor mode. See
parameter group 4-8* Power
Limit
.
[232] Power limit
gen.
N O T I C E
This option is only available in FC 302.
Serves as input to activate the power limit function in the generating mode. See
parameter group 4-8*
Power Limit
.
[233] Power limit
both
N O T I C E
This option is only available in FC 302.
Serves as input to activate the power limit function in both the motor and the generating mode. See
parameter group 4-8* Power Limit
.
[234] Light load +
evacuation
N O T I C E
This option is only available in FC 302.
Use this option to activate both light-load detection and evacuation.
AU275636650261en-000101 / 130R0334
188 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide