Troubleshooting
Check if the motor shaft is locked.
Check if the start current triggers the current limit set in
parameter 4-18 Current Limit
.
Check if it increases the value in
parameter 30-23 Locked Rotor Detection Time [s]
.
7.2.86 WARNING/ALARM 104, Mixing Fan Fault
Cause
The fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is turned on. The
mixing fan fault can be configured as a warning or an alarm in
parameter 14-53 Fan Monitor
.
Troubleshooting
Cycle power to the drive to determine if the warning/alarm returns.
7.2.87 WARNING/ALARM 122, Mot. Rotat. Unexp.
Cause
The drive performs a function that requires the motor to be at standstill, for example DC hold for PM motors.
7.2.88 WARNING 123, Motor Mod. Changed
Cause
The motor selected in
parameter 1-11 Motor Model
is not correct.
Troubleshooting
Check the motor model.
7.2.89 WARNING/ALARM 157, Power Limit Mot.
Cause
The output power exceeds the value defined in
parameter 4-82 Power Limit Motor Mode
.
7.2.90 WARNING/ALARM 158, Power Limit Gen.
Cause
The generating power exceeds the value defined in
parameter 4-83 Power Limit Generator Mode
.
7.2.91 WARNING 163, ATEX ETR Cur.Lim.Warning
Cause
The drive has run above the characteristic curve for more than 50 s. The warning is activated at 83% and deactivated at 65% of the
allowed thermal overload.
7.2.92 ALARM 164, ATEX ETR Cur.Lim.Alarm
Cause
Running above the characteristic curve for more than 60 s within a period of 600 s activates the alarm, and the drive trips.
7.2.93 WARNING 165, ATEX ETR Freq.Lim.Warning
Cause
The drive has run for more than 50 s below the allowed minimum frequency (
parameter 1-98 ATEX ETR Interpol. Points Freq.
).
7.2.94 ALARM 166, ATEX ETR Freq.Lim.Alarm
Cause
The drive has run for more than 60 s (in a period of 600 s) below the allowed minimum frequency (
parameter 1-98 ATEX ETR Interpol.
Points. Freq.
).
7.2.95 WARNING/ALARM 210, Position Tracking
Cause
The actual position error exceeds the value in
parameter 4-71 Maximum Position Error
.
Parameter 4-70 Position Error Function
defines
whether this is a warning or an alarm.
AU275636650261en-000101 / 130R0334
714 | Danfoss A/S © 2022.12
Troubleshooting
VLT AutomationDrive FC 301/302