Parameter 36-42 Terminal X49/7 Min Scale
Table 1332: Parameter 36-42 Terminal X49/7 Min Scale
36-42 Terminal X49/7 Min Scale
Default value: 0%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Match the minimum output of terminal X49/7 with a required value. The required value is defined as a percentage of the value
selected in
parameter 36-40 Terminal X49/7 Analogue Output
. To know more about how this parameter works, see
parameter 6-52
Terminal 42 Output Max Scale
. The following example describes how the drive uses this parameter.
Example:
Parameter 36-03 Terminal X49/7 Mode
=
[0] Voltage 0–10 V
.
Parameter 36-40 Terminal X49/7 Analogue Output
=
[100] Output frequency
.
Parameter 4-19 Max Output Frequency
= 200 Hz.
Application requirement: If the output frequency is lower than 20 Hz, the output of terminal X49/7 should be 0 V. To fulfil the exam-
ple requirement, enter 10% in
parameter 36-42 Terminal X49/7 Min. Scale
.
Parameter 36-43 Terminal X49/7 Max. Scale
Table 1333: Parameter 36-43 Terminal X49/7 Max. Scale
Parameter 36-43 Terminal X49/7 Max. Scale
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Scale the maximum output of terminal X49/7. For example, the scaling is done for the following reasons:
To provide an output value lower than the maximum possible value.
To provide the full signal range using output values lower than a certain limit.
To know more about how this parameter works, see
parameter 6-52 Terminal 42 Output Max Scale
.
Example:
Parameter 36-03 Terminal X49/7 Mode
=
[0] Voltage 0–10 V
Parameter 36-40 Terminal X49/7 Analogue Output
=
[100] Output Frequency
.
Parameter 4-19 Max Output Frequency
= 200 Hz.
Example case 1:
5 V maximum output is required when the output frequency is 200 Hz.
Parameter 36-43 Terminal X49/7 Max. Scale
x
100% = 200%.
Example case 2:
10 V maximum output is required when the output frequency is 150 Hz (75% of the maximum out-
put frequency).
Parameter 36-43 Terminal X49/7 Max. Scale
= 75%.
AU275636650261en-000101 / 130R0334
648 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide