
•
•
6.3 Control
6.3.1 Control Loops
In positioning and synchronization mode, 2 extra control loops control the motor in addition to the motor controller running flux
control principle, sensorless, or with motor feedback. The position PI controller is the outer loop providing the setpoint for the
speed PID, which provides the reference for the motor controller. For a closed loop, feedback source can be selected individually for
each of 3 controllers.
For sensorless control principle, select
[0] Motor feedb. P1-02
in the following parameters:
Speed PID:
Parameter 7-00 Speed PID Feedback Source
.
Position PI:
Parameter 7-90 Position PI Feedback Source.
With this set-up, both controllers use the motor angle calculated by the motor controller. See
for control structure
and parameters affecting the control behavior.
Commanded
Position
Speed
+
Speed Limit
Max
Min
Accel. limit
+
Par. 7-99
Par. 4-1*
7-9*
Position
PI Ctrl.
Par. 7-98
Position
PI
Feed
Par.7-90 Position PI
Feedback Source
Par. 7-00 Speed PID
Feedback Source
7-0*
Speed PID
Par. 7-08
Speed PID
Accel. Feed forward
factor
Flux motor
control
Ramp
Torque
Acceleration
Par.1-69 System Inertia
e3
0b
e7
76
.1
0
Profile
Generator
Illustration 105: Positioning and Synchronization Mode
6.3.2 Control and Status Signals
IMC control and status signals are available I/O bits and fieldbus bits.
Table 1431: Control and Status Signals
Name
Function
Digital
input
(1)
Control
word
Digital
output
Status
word
Control signals
Enable master offset
Activates the master offset when
parameter 17-93 Master
Offset Selection
is set to options
[0]
–
[5]
.
x
x
–
Start homing
Starts selected homing function.
x
x
–
–
Start virtual master
Starts the virtual master.
x
x
–
–
Activate touch
Selects touch probe positioning mode.
x
x
–
–
Relative position
Selects between absolute and relative positioning.
x
x
–
–
Enable reference
Starts selected motion.
x
x
–
–
Sync. to position
mode
Selects positioning in synchronizing mode.
x
x
–
–
AU275636650261en-000101 / 130R0334
686 | Danfoss A/S © 2022.12
Integrated Motion Controller
VLT AutomationDrive FC 301/302
Programming Guide