Page 2-24
MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Gas or Vacuum Lost
Chapter 2: Troubleshooting Procedures
3. Replace the wiring between the Area Alarm Module and the transducer. If
this solves the problem go to “Final Actions” on page 2-7. Otherwise, call
BeaconMedæs Technical Support.
2.18 Gas or Vacuum Lost
1. A type of
gas
or
vacuum
and the word
Lost
displays on the Master Alarm.
Yes
No
L J
Go to “Final Actions” on page 2-7.
2. The Area Alarm, at the location showing on the Master Alarm’s display, is
powered on.
Yes
No
L J
Turn the power to the Area Alarm on (see “Area Alarm Power-
Up” on page 1–112). If this solves the problem, go to “Final
Actions” on page 2-7. Otherwise, go to step 4.
SHOCK HAZARD
The potential for electric shock exists with electrical equipment. Use cau-
tion when troubleshooting any electrical device.
3. Use caution while checking voltage inside the Area Alarm.
4. The voltage across the two orange lead connections on the breakout board is
approximately 20 V AC. Refer to the wiring diagram FO 3-4 at the rear of
this manual.
Yes
No
L J
Replace the transformer (refer to procedure 4.5 on page 4-16). If
this solves the problem, go to “Final Actions” on page 2-7.
Otherwise, go to step 5.
5. Check the LEDs on the Network Communications Board (see “Area Alarm
Power-Up” on page 1–112). The LEDs that indicate whether the alarm is
communicating are operating correctly.
Yes
No
L J
Call BeaconMedæs Technical Support.
Содержание MedPlus TotalAlert
Страница 13: ...Page xii MedPlus TotalAlert Alarm Network Operation and Maintenance Manual 205728 Table of Contents NOTES...
Страница 17: ...Page 1 4 MedPlus TotalAlert Alarm Network Operation and Maintenance Manual 205728 Chapter 1 Introduction NOTES...
Страница 203: ...Page 3 2 MedPlus TotalAlert Alarm Network Operation and Maintenance Manual 205728 Chapter 3 Theory of Operation NOTES...
Страница 289: ...Page 5 2 MedPlus TotalAlert Alarm Network Operation and Maintenance Manual 205728 Chapter 5 Parts List NOTES...
Страница 367: ...Page 7 2 MedPlus TotalAlert Alarm Network Operation and Maintenance Manual 205728 Chapter 7 Accessories NOTES...
Страница 370: ...Schematic Wiring Diagram Typical Local Alarm...
Страница 371: ...Schematic Wiring Diagram Typical Master Alarm...
Страница 372: ...Schematic Wiring Diagram Typical Master Alarm to Master Alarm...
Страница 373: ...Schematic Wiring Diagram Typical Area Alarm...
Страница 374: ...Schematic Wiring Diagram Typical Master Alarm to Three Area Alarm...
Страница 375: ...Schematic Wiring Diagram Typical Master Alarm to Six Area Alarm Combination...