13-11
Chapter 13. Specifications
z
z
Standard conditions
Ambient temperature: 23 °C −2/+5 °C
Ambient humidity:
60 ±5 % RH
Power voltage:
105 V AC ±10 % (AC models)
24 V DC ±5 % (DC models)
Power supply frequency: 50 Hz ±1 % or 60 Hz ±1 % (AC models)
Vibration:
0 m/s2
Shock:
0 m/s2
Mounting angle:
Reference plane ±3° (main unit), no restriction (display
unit: separated from the main unit)
Space:
100 mm min. above and below, left and right, back and
front (main unit); gang mounting acceptable (display unit)
z
z
Operating conditions
Ambient temperature: 0 to 50 °C, 0 to 40 °C (when 2 or more main units are
gang-mounted)
0 to 50 °C (display unit)
Ambient humidity:
10 to 90 % RH (without condensation)
Rated power voltage:
100 to 240 V AC (operating input voltage 85 to 264 V AC,
AC models)
24 V DC (operating input voltage 20.4 to 28.8 V DC, DC
models)
Power supply frequency: 50 Hz ±2 % or 60 Hz ±2 % (AC models)
Vibration:
0 to 5 m/s2 (10 to 60 Hz for 2 h each in the x, y, and z
directions)
Shock:
0 to 100 m/s2
Mounting angle:
Reference plane ±10° (main unit), no restriction (display unit)
Elevation:
2000 m max.
Pollution degree:
2
Installation location:
Indoors
Space:
50 mm min. above and below
No space is needed around the display unit
z
z
Transport/storage conditions
Ambient temperature: −20 to +70 °C
Ambient humidity:
10 to 95 % RH (without condensation)
Vibration:
0 to 10 m/s2 (10 to 60 Hz for 2 h each in the x, y, and z
directions)
Shock:
0 to 300 m/s2 (3 times each in the x, y, and z directions)