10-12
Chapter 10. PLC Link Communication
The PLC link settings include the PLC connection settings, transfer settings, and data settings.
z
PLC connection settings
Setting item
Settings
Initial value
Notes
IP address
0.0.0.1 to 255.255.255.254
192.168.255.10
Port
0 to 65535
1025
Number of retries
0 to 10 times
3
Timeout time
100 to 6000 ms
1000
Transmission delay time
0 to 1000 ms
0
Cyclic transfer scan cycle
100 to 1000 ms
200
Triggered transfer scan cycle
100 to 1000 ms
500
Startup delay time
0 to 60 s
5
Trigger device initialization
0: No
1: Yes
1
Notification device initialization 0: No
1: Yes
0
z
Transfer settings
Transfer sheets 1 to 4 can be set independently.
Setting item
Settings
Initial value
Notes
Transfer type
Cyclic data transfer (PLC
→
C7G)
Cyclic data transfer (C7G
→
PLC)
Triggered data transfer (PLC
→
C7G)
Triggered data transfer (C7G
→
PLC)
Not set
Trigger device address
[When trigger device is PLC]
See the list of address ranges for the
PLC device type.
[When trigger device is C7G]
Selectable from the C7G monitor
data and parameters.
Not set
For triggered data transfer
Live notification device address See the list of address ranges for the
PLC device type.
Not set
For cyclic data transfer
Completion notification bit
address
See the list of address ranges for the
PLC device type.
Not set
Completion notification data
address
See the list of address ranges for the
PLC device type.
Not set
Handling Precautions
•
If the firmware version of the MAIN block is 3.x.x (where x stands for any
number), completion notification data can be set, but it is not written.
10 - 3 List of PLC Link Settings