6-27
Chapter 6. Display and Setting Data
z
Logical operation bank
Bank selection: LOGICAL OPERATION
Loop selection: None
Group selection: Groups 1 to 32
z
z
Logical operations Groups 1 to 32 (common)
Item display
Item
Settings
Initial
value
Communication
Notes
Read
Write
RAM EEPROM
Operation type
Calculation type
1: Logical Operation 1
(A and B) or (C and D)
2: Logical Operation 2
(A or B) And (C or D)
3: Logical Operation 3
(A or B or C or D)
4: Logical Operation 4
(A and B and C and D)
1
#
*
Input assignment A Input assignment A
1024 to 2047
(Standard bit code)
1024
#
*
Rising is detected
if the target data
is set to ON at
power-on when
the setting is "2:
Rising."
Falling is not
detected if the
target data is
set to OFF at
power-on when
the setting is "3:
Falling."
Input assignment B Input assignment B
1024
#
*
Input assignment C Input assignment C
1024
#
*
Input assignment D Input assignment D
1024
#
*
Input bit polarity A
Input bit polarity A
0: Direct
1: Reverse
2: Rising
3: Falling
0
#
*
Input bit polarity B
Input bit polarity B
0
#
*
Input bit polarity C
Input bit polarity C
0
#
*
Input bit polarity D
Input bit polarity D
0
#
*
ON delay
ON delay time
0.0000 to 3200.0 s
0.0000
#
*
The time
resolution of the
operation is the
sampling cycle.
With decimal
point
OFF delay
OFF delay time
0.0000 to 3200.0 s
0.0000
#
*
Inversion
Inversion
0: Direct
1: Reverse
0
#
*
Handling Precautions
•
If the version of the MAIN block firmware is earlier than 6.x.x (where x stands
for any number), the available logical operation groups are groups 1 to 16.