13-5
Chapter 13. Specifications
Differential for ON/OFF control:
0 to 32000 (5 digits max. within this range, 4 digits max.
after the decimal point)
SP
Number of LSP groups for constant value operation: 8 (per loop)
Number of patterns for pattern operation:
16 (common to all loops)
Number of segments for pattern operation:
Up to 16 (for each pattern)
z
z
AO-C block
z
z
Current output × 1
Type:
4–20 or 0–20 mA DC
Output type:
Select from control output (MV), process value (PV),
set value (SP), standard number, etc.
Accuracy:
0.1 % FS
Allowable load resistance:
600 Ω max.
Output resolution:
1/16000 min.
z
z
CT (current) input × 1
Recommended current transformers:
QN206A (hole diameter: 5.8 mm, 800 turns),
QN212A (hole diameter:12 mm, 800 turns) Note:
Not UL-certified
Current measurement range: 0.4 to 50.0 A AC, 50/60 Hz (peak current: 71 A
max. with 800 turns and 1 pass of the power wire)
Maximum allowable current: 70 A AC (peak current: 99 A max. with 800 turns
and 1 pass of the power wire)
Indication accuracy:
±1 % FS ±1 digit (under standard conditions; does
not include CT accuracy)
Indication resolution:
0.1 A AC
Indication update cycle:
100 ms
z
z
VT (voltage) input × 1
Recommended voltage transformer:
81406725-003 (not UL-certified)
Voltage measurement range: 24 to 240 V AC, 50 Hz/60 Hz (peak voltage: 339 V
max., recommended voltage: transformer primary
side 200 V, secondary side 10 V)
Maximum allowable voltage: 264 V AC (peak voltage 373 V max., recommended
voltage:
transformer primary side 200 V,