![Azbil C7G Скачать руководство пользователя страница 293](http://html1.mh-extra.com/html/azbil/c7g/c7g_installation-and-configuration-manual_3042606293.webp)
6-47
Chapter 6. Display and Setting Data
z
Pattern bank
Bank selection: PATTERN
Pattern selection: Patterns 1 to 16
Segment selection: None
The table below lists the relevant items for one pattern. These items are the same for
patterns 1 to 16.
z
z
Pattern settings
Item display
Item
Settings
Initial
value
Communication
Notes
Read
Write
RAM EEPROM
Number of
segments
Number of segments
1 to 16
16
G.SOAK time
G.SOAK time
0.0000 to 300.00 s
2.0000
With decimal point
PV start
PV start
0: Disable PV start
1: Enable PV start
0
PV start is only possible
for segment 2.
Cycle
Cycle
0 to 32000 times
0
Pattern link
Pattern link
0: No link
1 to 16: Link
destination
pattern
number
0
End of operation
End of operation
0: READY
1: END
2: Constant value
operation
0
Handling Precautions
•
If the version of the MAIN block firmware is earlier than 6.x.x (where x stands
for any number), there is no pattern bank.
Note
•
When pattern settings are written via communication, RAM and EEPROM (the