4-92
Chapter 4. Functions
(2) Set the linearization table.
Item (bank)
Display
Description
Initial value
Operation type
(Linearization table bank)
MENU > Linearization Table
Operation type
0: Breakpoint
1: Bias
0
Breakpoint A1
(Linearization table bank)
MENU > LinearizationTable
Breakpoint A1
0
-32000
Breakpoint A2
(Linearization table bank)
MENU > LinearizationTable
Breakpoint A2
17.4
32000
Breakpoint A3
(Linearization table bank)
MENU > LinearizationTable
Breakpoint A3
25
0.0000
...
Breakpoint A8
(Linearization table bank)
MENU > LinearizationTable
Breakpoint A18
75
0.0000
Breakpoint A9
(Linearization table bank)
MENU > LinearizationTable
Breakpoint A19
82.6
0.0000
Breakpoint A10
(Linearization table bank)
MENU > LinearizationTable
Breakpoint A20
100
0.0000
Breakpoint B1
(Linearization table bank)
MENU > LinearizationTable
Breakpoint B1
0
-32000
Breakpoint B2
(Linearization table bank)
MENU > LinearizationTable
Breakpoint B2
10
32000
Breakpoint B3
(Linearization table bank)
MENU > LinearizationTable
Breakpoint B3
15
0.0000
...
Breakpoint B8
(Linearization table bank)
MENU > LinearizationTable
Breakpoint B18
85
0.0000
Breakpoint B9
(Linearization table bank)
MENU > LinearizationTable
Breakpoint B19
90
0.0000
Breakpoint B10
(Linearization table bank)
MENU > LinearizationTable
Breakpoint B20
100
0.0000
z
Example using linear approximation for analog output
This is an example of using linearization table groups 3 and 4 for analog output of
the A2 slot by specifying them by DI (digital input).
An output of 0.0 to 100.0 % is converted to other characteristics of 0.0 to 100.0 %.
The linearization table group having the value obtained by adding the linearization
table group number specified in the analog output bank setting to the linearization
table group number selected by the DI setting is selected.
When group 3 is specified in the analog output bank setting and group 0 or group 1
is set to be selected by DI, group 3 will be selected when DI is OFF, since 3 + 0 = 3,
and group 4 will be selected when DI is ON, since 3 + 1 = 4.