4-46
Chapter 4. Functions
z
Pattern start number
The pattern start number can be set for each loop.
There are two ways to select the pattern number when the mode switches from
READY to RUN, i.e., when pattern operation starts.
•
The pattern start number can be set on the display unit screen or via
communication.
•
Add the base number to the pattern number specified by the DI and set it as the
pattern start number.
Pattern start number setting
on the display unit screen
or via communication
When the sum of the pattern numbers
specified by DI is 0
When the sum of the pattern numbers specified by DI is not 0
+
Pattern start No. low/high limits
Pattern No. where operation starts
Sum of the pattern Nos.
specified by DI
Base number
(pattern start No. low limit − 1)
The pattern start number, pattern start number low limit, and pattern start number
high limit can be set for each loop.
Item
Display
Description
Initial value
Pattern start number
(Pattern configuration bank)
MENU > PatternConfig
PTN start number
1 to 16
1
Pattern start number low limit
(Pattern configuration bank)
MENU > PatternConfig
PTN start number low limit
1 to 16
1
Pattern start number high limit
(Pattern configuration bank)
MENU > PatternConfig
PTN start number high limit
1 to 16
16
The base number for the pattern selection by DI is the value obtained by
subtracting 1 from the pattern start number low limit.
The value obtained by adding the base number to the sum of the pattern numbers
specified by DI is the pattern number at which operation is started.