4-45
Chapter 4. Functions
Handling Precautions
•
If cycle operation is set for the source of a link, the pattern link operates after
the cycle operation is completed.
•
If the pattern number of the link source is set for the pattern link, the pattern
will be repeated endlessly.
z
End of operation
The state after the end of pattern operation can be set for each pattern.
If “0: READY” is set, operation will end in READY mode.
If “1: END” is set, operation will end in RUN-END mode.
If “2: Constant value operation” is set, operation will transition to constant value
operation in RUN mode.
Item
Display
Description
Initial value
End of operation
(Pattern bank)
MENU > Pattern
End of operation
0: READY
1: END
2: Constant value operation
0
Handling Precautions
•
If one time (1 repetition) or more is set in the cycle count, the device enters the
end of operation state after the cycle(s) are completed.
•
If a link destination is set in pattern link, instead of entering the end of
operation state, the device will execute the pattern operation of the link
destination.
•
1 - 6 Operation Modes (p. 1-23) (diagram of mode transitions)
•
If the device enters the RUN-END mode at the end of operation, the mode
will not be retained if a power failure occurs. When the power is restored, the
device starts operation in the RUN mode from segment 1 of the pattern start
number.
•
If the device enters the READY mode or the constant value operation mode at
the end of operation, the mode will be retained even if a power failure occurs.