![Azbil C7G Скачать руководство пользователя страница 178](http://html1.mh-extra.com/html/azbil/c7g/c7g_installation-and-configuration-manual_3042606178.webp)
4-108
Chapter 4. Functions
Item
"Data selection" setting
Standard
Custom
Ring
Recording
operation
Recording cycle
Selected from "Same as sampling
cycle, 0.1 s, 1 s, 10 s, 1 min, and 10
min."
Same as on the left
Same as on the left
Start and stop
Selected from "DI1 to 2, events 1 to
16, and standard bit code"
and Standard Numerical Codes
(p. 14-6)
Same as on the left
Same as on the left
Alarm concerning
the number of files
and capacity
An SD card error alarm is issued in
any of the following cases.
•
When there is an attempt to write
data exceeding the capacity of the
microSD memory card
•
When there is an attempt to write
a new file when there are 1,000
files in BLK64 (the last folder)
Same as on the left
No alarm occurs as the oldest
file is rewritten (however, if
files recorded by standard or
custom recording remain, an
alarm may be issued).
* It is necessary to configure the settings for the health index.
Start the CDS and health index at the start of batch processing, and stop the CDS and health index when batch processing ends.
4 - 20 Health Index (p. 4-116)
z
z
Sections (Standard)
Section
Data
Notes
Context section
(From Section Context to
SectionEnd)
P (Proportional band)
Records the setting when CDS starts.
I (Integral time)
D (Derivative time)
OL (MV low limit)
OH (MV high limit)
SP high limit
Specific R value
(Diagnostic parameter)
Normalization responsiveness (Kp/Tp)
(Gain is defined as Kp and time constant as Tp in the transfer
function.)
Calculated from the data when the PV is rising during batch
processing.
Records the definite value when CDS ends.
Time sequence data section
(From Section TemporalData
to SectionEnd)
(Updated in each recording
cycle)
Timestamp
Year/Month/Date Hour:Minutes:Seconds. Milliseconds
SP
PV
MV
R value
DT5
Varies depending on the type of output block to which the MV is
assigned.
AO-C block: RMS current (CT)
V-P block: RMS current (CT1)
Other than the above: Fixed at 0
(Fixed at 0 when Heat MV or Cool MV is assigned)
DT6
Varies depending on the type of output block to which the MV is
assigned.
AO-C block: RMS voltage (VT)
V-P block: RMS current (CT2)
Other than the above: Fixed at 0
(Fixed at 0 when Heat MV or Cool MV is assigned)
DT7
Varies depending on the type of output block to which the MV is
assigned.
AO-C block: Actuator (heater) resistance
(Calculated using the CT input current and the VT
input voltage)
Other than AO-C block: Fixed at 0
DT8
Fixed at 0
DT9
DT10