![Azbil C7G Скачать руководство пользователя страница 253](http://html1.mh-extra.com/html/azbil/c7g/c7g_installation-and-configuration-manual_3042606253.webp)
6-7
Chapter 6. Display and Setting Data
z
EVENT bank
Bank selection: EVENT
Loop selection: None
Group selection: Event groups 1 to 16
z
z
Event groups 1 to 16 (common)
Item display
Item
Settings
Initial
value
Communication
Notes
Read
Write
RAM EEPROM
Event main
setting
Main setting
−32000 to +32000
0.0000
#
*
Depending on
the setting for the
operation type of
each event group
in the Event Config
bank, it may not
be necessary to
set some of the
values shown at
left. However, all
of the values are
displayed and can
be specified.
With decimal point
Event subsetting
Subsetting
−32000 to +32000
0.0000
#
*
Hysteresis
Hysteresis
0.0000 to 32000
5.0000
#
*
ON delay
ON delay time
0.0000 to 3200.0 s
0.0000
#
*
OFF delay
OFF delay time
0.0000 to 3200.0 s
0.0000
#
*
z
PID bank
Bank selection: PID
Loop selection: Loops 1 to 4
Group selection: PID groups 1 to 8
z
z
Loop1 to 4 / PID groups 1 to 8 (common)
Item display
Item
Settings
Initial
value
Communication
Notes
Read
Write
RAM EEPROM
P
(Proportional band)
P(Proportional band)
0.1000 to 3200.0 %
5.0000
#
*
With decimal
point
I (Integral time)
I(Integral time)
0.0000 to 32000 s
120.00
#
*
With decimal
point
D
(Derivative time)
D(Derivative time)
0.0000 to 32000 s
30.000
#
*
With decimal
point
RE (Manual reset) RE(Manual reset)
-10.000 to +110.00 %
50.000
#
*
Enabled when
the integral time
of the same PID
group is 0.
With decimal point
OL (MV low limit) OL(MV low limit)
-10.000 to +110.00 %
0.0000
#
*
With decimal point
OH (MV high limit)
OH(MV high limit)
-10.000 to +110.00 %
100.00
#
*
With decimal point
Cool P
(Proportional band)
Proportional band for
cooling
0.1000 to 3200.0 %
5.0000
#
*
With decimal point
Cool I
(Integral time)
Integral time for
cooling
0.0000 to 32000 s
120.00
#
*
With decimal point
Cool D
(Derivative time)
Derivative time for
cooling
0.0000 to 32000 s
30.000
#
*
With decimal point
Cool OL
(MV low limit)
MV low limit for
cooling
-10.000 to +110.00 %
0.0000
#
*
With decimal point
Cool OH
(MV high limit)
MV high limit for
cooling
-10.000 to +110.00 %
100.00
#
*