![Azbil C7G Скачать руководство пользователя страница 372](http://html1.mh-extra.com/html/azbil/c7g/c7g_installation-and-configuration-manual_3042606372.webp)
11-8
Chapter 11. Maintenance and Troubleshooting
z
The firmware version of the display unit does not match.
If the firmware version of the MAIN block and the HMI block (display unit) do
not match, necessary items may not be displayed, or unnecessary items may be
displayed on the monitor screen or parameter screen.
The correct combinations can be checked in the list of the release dates of each
firmware version in 14 - 4 Firmware Version History (p. 14-13).
The following can be performed using the SLP-C7 Smart Loader Package.
•
Checking the combination of firmware versions
•
Updating the firmware version of the HMI block (display unit)
(1) Start the SLP-C7.
(2) On the menu bar, select
[Help]
and then
[C7G Fi0rmware Update]
.
(3) The F/W version update screen appears.
(4) Click the
[Check Version]
button.
SLP-C7 checks the firmware version, and sequentially displays instruction
screens for when a firmware version update is required and when it is not
required.
For details, refer to the user's manual for SLP-C7.