4-66
Chapter 4. Functions
z
DO assignment
For the DI/DO terminals whose operation type is set to DO in the DI/DO
configuration bank and the terminals in the DO block, the output type can be set in
the DO configuration bank.
z
z
DI/DO
Item (bank)
Display
Description
Initial value
Output type of DI/DO 1 to 7
(DO configuration bank)
MENU > DO Config
DO 1/ Output type
0: OFF
1 to 10: Reserved
11: Event 1
12: Event 2
13: Event 3
14: Event 4
15: Event 5
16: Event 6
17: Event 7
18: Event 8
19: Event 9
20: Event 10
21: Event 11
22: Event 12
23: Event 13
24: Event 14
25: Event 15
26: Event 16
27 to 1023: Reserved
1024 to 2047: Standard bits
14 - 2 Standard Bit Codes and Standard
0
MENU > DO Config
DO2 / Output type
MENU > DO Config
DO3 / Output type
MENU > DO Config
DO4 / Output type
MENU > DO Config
DO5 / Output type
MENU > DO Config
DO6 / Output type
MENU > DO Config
DO7 / Output type
Handling Precautions
•
The output type setting is valid only for a DI/DO number that is set for DO in
the DI/DO configuration bank. If the DO output type is set for a number set to
DI in the DI/DO configuration bank, the number cannot be used for output.
•
This product forces DO output OFF and displays an alarm when an overcurrent
is detected in the DO terminal in order to protect the output circuits. Check
the loads and wiring to prevent overcurrent from occurring.
•
If the version of the MAIN block firmware is earlier than 6.x.x (where x stands
for any number), "DO Config" is displayed as "DO," and "DO1" to "DO7" are
displayed as "GROUP1" to "GROUP7."