5-21
Chapter 5. Screens
z
1-loop monitor screen during MFB AT
If a value of 1, 2, or 11 to 14 is set for "Output Type" in the PP (position
proportional) bank, the motor drive output status can be displayed by displaying
the 1-loop monitor screen of the relevant loop.
The figure below shows the screen's appearance during MFB AT (MFB auto-
tuning).
(4)
(1)
(2)
(3)
(1)
[MFB AT STOP]
button
Touching this stops the MFB AT and changes to the MFB AT stopped screen.
(2) Displays the status of motor drive output.
OPEN: OPEN relay status → Lit: ON, Not lit: OFF
CLOSE: CLOSE relay status → Lit: ON, Not lit: OFF
(3) Displays MFB input count.
When MFB AT ends, the counts at the fully-closed position and fully-opened
position are saved to "Fully closed MFB count" and "Fully open MFB count" in
the PP (positional proportional) bank.
(4) View change button
Touching this icon changes the display. This enables viewing of MV graphs and
other content.
Handling Precautions
•
If a value other than 1, 2, and 11 to 14 is set for "Output Type" in the PP
(position proportional) bank, the motor drive output status is not displayed on
the 1-loop monitor screen.
•
If the "Control method selection" setting of the PP (position proportional)
bank is set to 2 or 3, MFB AT is not executed.
•
If an MFB input wiring disconnection is detected, MFB AT does not start. Also,
if an MFB input wiring disconnection is detected after starting MFB AT, the
MFB AT process is stopped.