4-115
Chapter 4. Functions
z
Specifications of older versions
Older versions of the MAIN block firmware have specifications that are different
from those of the current version described in the following table.
Version (x stands
for any number)
Difference from the current specifications
5.x.x
•
Ring recording is not available.
•
"2: Ring" cannot be selected in Data selection.
•
When Data selection is set to "0: Standard" and the recording cycle is set to 10 ms, and when a
loop type with two or more loops is set, the recording cycle is automatically set to 50 ms.
•
When Data selection is set to "1: Custom" and the recording cycle is set to 10 ms, and when the
number of data items is more than 10, only 10 data items from Data1 to 10 are recorded.
•
When Data selection is set to "1: Custom," the file name is "XXXYYYYZ.csv."
XXX: Number of power ON/OFF cycles of the equipment (hexadecimal)
YYYY: Number of CDS files created since power ON (hexadecimal)
Z:
File division classification (0: first file, 1: following file)
•
There is no data number in the header line of files recorded by custom recording.
4.x.x
•
Ring and custom recording are not available.
•
The setting items "Data selection," "Number of data," and "Data1" to "Data40" are not available.
•
When the recording cycle is set to 10 ms and a loop type with two or more loops is set, the
recording cycle is automatically set to 50 ms.
3.x.x
•
Ring and custom recording are not available.
•
The setting items "Data selection," "Number of data," and "Data1" to "Data40" are not available.
•
When the recording cycle is set to 10 ms and a loop type with two or more loops is set, the
recording cycle is automatically set to 50 ms.
•
The power-on date and time is "2014/1/1 00:00:00 (YYYYMMDD HH:MM:SS)."
•
The date and time cannot be set from the device display unit.
•
The CDS cannot be started using events 9 to 16 or standard bit codes.
2.x.x
•
Ring and custom recording are not available.
•
The setting items "Data selection," "Number of data," and "Data1" to "Data40" are not available.
•
When the recording cycle is set to 10 ms and a loop type with two or more loops is set, the
recording cycle is automatically set to 50 ms.
•
The power-on date and time is "2014/1/1 00:00:00 (YYYYMMDD HH:MM:SS)."
•
The date and time cannot be set from the device display unit.
•
The CDS cannot be started using events 1 to 16 or standard bit codes.