4-32
Chapter 4. Functions
z
Setting the LSP from the 1-loop monitor screen
(1) Press the
[SP]
button on the 1-loop monitor screen.
> The SP change screen appears.
(2) Press the Change button on the right side of "LSP_VALUE."
> The LSP value setting screen appears.
(3) Enter a value using the numeric keypad, and press the
[ENTER]
button to set
the LSP that is being used (from among LSP1 to 8) to that value.
Handling Precautions
•
Input values within the SP low–high limit range and the PV range are valid. If
the input value is invalid, the LSP does not change.
•
If the version of the MAIN block firmware is earlier than 6.x.x (where x stands
for any number), the input value setting range is fixed to "−32000 to +32000."
•
Parameter setting: The setting range of the SP for LSP groups 1 to 8 in the SP
bank is fixed to "−32000 to +32000."
z
Selecting LSP group and RSP from the 1-loop monitor screen
(1) Press the
[SP]
button on the 1-loop monitor screen.
> The SP change screen appears.
(2) Press the Change button on the right side of "LSP/RSP."
> The LSP/RSP selection screen appears.
(3) Press the
[LSP]
button of the LSP group to be used.
> The mode is switched to LSP, and the selection of the LSP group is complete.
Also, press the
[RSP]
button to switch the mode to RSP.
z
Number of LSP system groups
The number of LSP groups to be used can be selected for each control loop.
Item (bank)
Display
Description
Initial value
Number of LSP system groups
(SP configuration bank)
MENU > SP Config
Number of SP system groups
1 to 8
1
z
RSP setting
RSP can be set with the AI bank assigned to RSP.
•
Range type
•
Linear scaling low and high limits
•
Ratio
•
Bias
•
Filter