![Azbil C7G Скачать руководство пользователя страница 262](http://html1.mh-extra.com/html/azbil/c7g/c7g_installation-and-configuration-manual_3042606262.webp)
6-16
Chapter 6. Display and Setting Data
z
ANALOG OUTPUT bank
Bank selection: ANALOG OUTPUT
Block selection: A2, B2, A1, B1
Group selection: None
z
z
Blocks A2, B2, A1, and B1 (common)
Item display
Item
Settings
Initial
value
Communication
Notes
Read
Write
RAM EEPROM
Output range
Output range
0: 4–20 mA
1: 0–20 mA
0
-
Output type
Output type
0: Fixed at 0 %
1: MV
2: Heat MV
(for heating/cooling
control)
3: Cool MV
(for heating/cooling
control)
4: PV
5: SP
6: Deviation (PV − SP)
7 to 2047: Reserved
2048 to 3071:
Standard numerical
codes
Codes and Standard
Numerical Codes
(p. 14-6)
1
#
*
Loop definition
Loop definition
1: Loop 1
2: Loop 2
3: Loop 3
4: Loop 4
1
#
*
Output scaling
low limit
Output scaling low
limit
−32000 to +32000
0.0000
#
*
With decimal point
Output scaling
high limit
Output scaling high
limit
−32000 to +32000
100.00
#
*
With decimal point
Linearization
table group
Linearization table
group definition
0: No linearization
1 to 8
0
#
*