6-34
Chapter 6. Display and Setting Data
Item display
Item
Settings
Initial
value
Communication
Notes
Read
Write
RAM EEPROM
Auto-tuning
Auto-tuning
0: Auto-tuning stop
1: Auto-tuning start
2: Auto-tuning not
implemented
3: Auto-tuning
completed
4: Auto-tuning failed
2
-
0 and 1 can be set
but are not saved.
2 to 4 are saved
automatically
when auto-tuning
finishes, but can
also be set and
saved manually.
Fully closed MFB
count
Fully closed MFB
count
0 to 8000
2000
-
-
-
Saved
automatically
when auto-tuning
finishes normally,
but can also be
set and saved
manually.
Full opening MFB
count
Fully open MFB count 0 to 8000
6000
-
-
-
Full opening time Full opening time
5.0000 to 240.00 s
40.000
-
-
-
Linearization
table group
Linearization table
definition
0: No linearization
1 to 8
0
#
*