13-10
Chapter 13. Specifications
DC models
1500 V AC, 1 min
Between motor block output terminals (#1 to #3)
and frame ground terminal (#3)
Between motor block output terminals (#1 to #3)
and DC power supply terminals (#1 or #2)
Between motor block output terminals (#1 to #3)
and secondary terminals (excluding motor block
output terminals (#1 to #3))
500 V AC for 1 min
Between DC power supply terminals (#1 or #2) and
frame ground terminal (#3)
Between DC power supply terminals (#1 or #2) and
secondary terminals (except for motor block output
terminals (#1 to #3))
Case material:
Main unit: Modified PPE (case), PC (board holder,
front mask)
Display unit: Modified PPE (case), PET film (protective
sheet)
Case color:
Black
Applicable standards:
EN 61010-1, EN 61326-1 (for use in industrial location)
During EMC testing, the reading or output may fluctuate
by ±10 % FS.
cULus: UL 61010-1, CSA C22.2 No. 61010-1 (applicable
model needs to be selected)
Overvoltage category: Category II (IEC 60364-4-443, IEC 60664-1)
Installation:
Main unit: Mounting on a DIN rail (standard) or
on the display unit using the integrating
bracket
Display unit: Mounting using dia. 3 mm screws
(standard) or the integrating bracket
(mount in a 92 × 92 mm hole)
Weight:
Main unit:
500 g max.
Display unit:
150 g max.
Integrating bracket : 150 g max.
Accuracy of built-in clock:
Monthly error less than ±140 s
Resets to 2000/01/01 00:00:00 (initial value) at each
power-on (including recovery from power loss).
However, resets to 2014/01/01 00:00:00 (initial value) if
firmware version of the MAIN block is 3.x.x or earlier.
When the CLOCK block is used, accuracy is according to
its specifications.
Pattern operation: Monthly error less than ±140 s