10-8
Chapter 10. PLC Link Communication
z
Transfer setting examples
z
z
Cyclic data transfer (PLC
→
C7)
Used for continuously writing parameters from the PLC to the C7.
In this example, data items D0000100 to D0000103 are converted to data with 1
digit after the decimal point and transferred to the C7 periodically.
z
z
Transfer operation settings
Transfer type
Cyclic data transfer (PLC → C7)
Live notification device
M0000100
Device to receive completion notification bit
M0000010
Device to receive completion notification data D0000010
z
z
Transfer data settings
D0000100 → Loop1: (RAM) Current LSP
Decimal place 1
D0000101 → Loop1: (RAM) Current proportional band Decimal place 1
D0000102 → Loop1: (RAM) Current integral time
Decimal place 1
D0000103 → Loop1: (RAM) Current derivative time
Decimal place 1
Handling Precautions
•
Use the RAM writing address when transferring (writing) to the C7
periodically.