DRV-28 inverter
s Function parameter list
-141-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P03.13
Torque reference
filter time
0.000
–10.000s
0.010s
○
P03.14
Source of upper
limit frequency
setup of forward
rotation in torque
control
0: Keypad (P03.16)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: Multi-step (the same as above)
6: MODBUS communication (the same as above)
7: PROFIBUS /CANopen/ DeviceNet communication
(the same as above)
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCat/Profinet communication
11: PLC
12: Reserved
0
○
P03.15
Source of upper
limit frequency
setup of reverse
rotation in torque
control
0: Keypad (P03.17)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: Multi-step (the same as above)
6: MODBUS communication (the same as above)
7: PROFIBUS /CANopen/ DeviceNet communication
(the same as above)
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCat/Profinet communication
11: PLC
12: Reserved
Note:
Source 1-11, 100% relative to the max.
frequency
0
○
P03.16
Keypad limit
value of upper
limit frequency of
forward rotation
in torque control
This function code is used to set frequency limit.
100% corresponds to the max. frequency. P03.16
sets the value when P03.14=1; P03.17 sets the
value when P03.15=1.
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
50.00Hz
○
P03.17
Max. output
frequency
50.00Hz
○