DRV-28 inverter
s Function parameter list
-151-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
motor VF control frequency)
P04.37
Reactive current
closed-loop
proportional
coefficient in
synchronous
motor VF
When the synchronous motor VF control mode is
enabled, this parameter is used to set the
proportional coefficient of the reactive current
closed-loop control.
Setting range: 0
–3000
50
○
P04.38
Reactive current
closed-loop
integral time in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the integral
coefficient of the reactive current closed-loop control.
Setting range: 0
–3000
30
○
P04.39
Reactive current
closed-loop
output limit in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the output limit
of the reactive current in the closed-loop control. A
greater value indicates a higher reactive closed-loop
compensation voltage and higher output power of
the motor. In general, you do not need to modify this
parameter.
Setting range: 0
–16000
8000
○
P04.40
Enable/disable IF
mode for
asynchronous
motor 1
0: Disabled
1: Enabled
0
◎
P04.41
Current setting in
IF mode for
asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0
–200.0%
120.0%
○
P04.42
Proportional
coefficient in IF
mode for
asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0
–5000
650
○
P04.43
Integral
coefficient in IF
mode for
asynchronous
When IF control is adopted for asynchronous motor
1, this parameter is used to set the inetgral
coefficient of the output current closed-loop control.
Setting range: 0
–5000
350
○