DRV-28 inverter
s Function parameter list
-195-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
between current communication and the next
communication exceeds the communication timeout
period, the system will report "485 communication
fault" (CE).
Under common situations, it is set to 0.0. In systems
which have continuous communication, users can
monitor the communication condition by setting this
parameter.
P14.05
Transmission
error processing
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(under communication control mode only)
3: Do not alarm and stop as per the stop mode
(under all control modes)
0
○
P14.06
Communication
processing action
0x00–0x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
0x00
○
P14.07–
P14.24
Reserved
variables
0–65535
0
●
P15 group Functions of communication extension card 1
P15.00–
P15.27
See the operation manual of communication extension card for details
P15.28
Master/slave
CAN
communication
address
0–127
1
◎
P15.29
Master/slave
CAN
communication
baud rate
selection
0: 50Kbps
1: 100 Kbps
2: 125Kbps
3: 250Kbps
4: 500Kbps
5: 1M bps
2
◎
P15.30
Master/slave
CAN
0.0 (invalid)–300.0s
0.0s
○