DRV-28 inverter
s Function parameter list
-157-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
Sln
REV
Previous
running
direction
Current
running
direction
ON
OFF→ON
Forward
Reverse
Reverse
Forward
ON
ON→OFF
Reverse
Forward
Forward
Reverse
ON→OFF
ON
Decelerate to stop
OFF
Sln: 3-wire control/Sin, FWD: Forward running, REV:
Reverse running
3: 3-wire control 2; This mode defines Sin as
enabling terminal. The running command is
generated by FWD or REV, and they control the
running direction. During running, the terminal Sin
should be closed, and terminal FWD or REV
generates a rising edge signal to control the running
and direction of inverter; the inverter should be
stopped by disconnecting terminal Sin.
FWD
REV
COM
Sln
SB2
SB1
SB3
Sln
FWD
REV
Running
direction
ON
OFF→ON
ON
Forward
OFF
Forward
ON
ON
OFF→ON
Reverse
OFF
Reverse
ON→OFF
Decelerate
to stop
Sln: 3-wire control/Sin, FWD: Forward running, REV: