DRV-28 inverter
s Basic operartion instructions
-98-
Function
code
Name
Detailed parameter description
Default
value
disabled
31: Counter trigger
32: Reserved
33: Clear frequency
increase/decrease setting
temporarily
34: DC brake
35: Switching between motor 1 and
motor 2
36: Command switches to keypad
37: Command switches to terminal
38: Command switches to
communication
39: Pre-exciting command
40: Zero out power consumption
quantity
41: Maintain power consumption
quantity
42: Source of upper torque limit
switches to keypad
56: Emergency stop
57: Motor over-temperature fault
input
59: Switch to V/F control
60: Switch to FVC control
61: PID polarity switch-over
66: Zero out encoder counting
67: Pulse increase
68: Enable pulse superimposition
69: Pulse decrease
70: Electronic gear selection
71–79: Reserved
P05.08
Polarity of input terminal
0x00
–0x3F
0x00
P05.09
Digital filter time
0.000
–1.000s
0.010s
P05.10
Virtual terminal setting
0x00–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
0x00