DRV-28 inverter
s Basic operartion instructions
-56-
Function
code
Name
Detailed parameter description
Default
value
same as above)
10: Set via pulse frequency HDIB (the
same as above)
11: Set via EtherCat/Profinet
communication
12: Set via PLC
Note: Set mode 2
–12, 100% corresponds
to three times of rated motor current.
P03.12
Torque set by keypad
-300.0%
–300.0% (rated motor current)
50.0%
P03.13
Torque reference filter time 0.000
–10.000s
0.010s
P03.14
Source of upper limit
frequency setup of forward
rotation in torque control
0: Keypad (P03.16)
1: AI1 (100% corresponds to max.
frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as
above)
5: Multi-step (the same as above)
6: MODBUS communication (the same as
above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as
above)
9: Pulse frequency HDIB (the same as
above)
10: EtherCat/Profinet communication
11: PLC
12: Reserved
Note: Source 1-11, 100% relative to the
max. frequency
0
P03.15
Source of upper limit
frequency setup of reverse
rotation in torque control
0: Keypad (P03.17)
1
–11: the same as P03.14
0
P03.16
Keypad limit value of upper
limit frequency of forward
rotation in torque control
Value range: 0.00 Hz
–P00.03 (Max. output
frequency)
50.00Hz
P03.17
Keypad limit value of upper
limit frequency of reverse
50.00Hz