DRV-28 inverter
s Function parameter list
-180-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
Hundreds:
0: Limit based on the max. frequency
1: Limit based on A frequency
Thousands:
0: A+B frequency, acceleration /deceleration of main
reference A frequency source buffering is invalid
1: A+B frequency, acceleration/ deceleration of main
reference A frequency source buffering is valid,
acceleration and deceleration are determined by
P08.04 (acceleration time 4).
P09.14
Low-frequency
proportional gain
(Kp)
0.00–100.00
Low-frequency
switching
point:
5.00Hz,
high-frequency switching point: 10.00Hz (P09.04
corresponds to high-frequency parameter), and the
middle is the linear interpolation between these two
points
1.00
○
P09.15
Acceleration/
deceleration time
of PID command
0.0–1000.0s
0.0s
○
P09.16
Filter time of PID
output
0.000–10.000s
0.000s
○
P09.17–
P09.28
Reserved
variables
0–65536
0
○
P10 group Simple PLC and multi-step speed control
P10.00
Simple PLC
mode
0: Stop after running once; the inverter stops
automatically after running for one cycle, and it can
be started only after receiving running command.
1: Keep running in the final value after running once;
The inverter keeps the running frequency and
direction of the last section after a single cycle.
2: Cyclic running; the inverter enters the next cycle
after completing one cycle until receiving stop
command and stops.
0
○
P10.01
Simple PLC
memory selection
0: No memory after power down
1: Memory after power down; PLC memories its
running stage and running frequency before power
down.
0
○
P10.02 Multi-step speed 0 Setting range of the frequency in 0
th
–15
th
sections
0.0%
○