DRV-28 inverter
s Function parameter list
-184-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P11.02
Reserved
variables
0–65535
0
○
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
1
○
P11.04
Overvoltage stall
protection
voltage
120–150% (standard bus voltage) (400V)
136%
○
120–150% (standard bus voltage) (230V)
120%
P11.05
Current-limit
selection
During accelerated running, as the load is too large,
the actual acceleration rate of motor is lower than
that of output frequency, if no measures are taken,
the inverter may trip due to overcurrent during
acceleration.
0x00–0x11
Ones: Current-limit action selection
0: Invalid
1: Always valid
Tens: Hardware current-limit overload alarm
selection
0: Valid
1: Invalid
01
◎
P11.06
Automatic
current-limit level
Current-limit protection function detects output
current during running, and compares it with the
current-limit level defined by P11.06, if it exceeds the
current-limit level, the inverter will run at stable
frequency during accelerated running, or run in
decreased
frequency
during
constant-speed
running; if it exceeds the current-limit level
continuously, the inverter output frequency will drop
continuously until reaching lower limit frequency.
When the output current is detected to be lower than
G model:
160.0%
P model:
120.0%
◎
P11.07
Frequency-drop
rate during
current limit
10.00
Hz/s
◎