DRV-28 inverter
s Basic operartion instructions
-102-
Set
value
Function
Description
37–40
Reserved
41
C_Y1
C_Y1 from PLC (You need to set P27.00 to 1.)
42
C_Y2
C_Y2 from PLC (You need to set P27.00 to 1.)
43
C_HDO
C_HDO from PLC (You need to set P27.00 to 1.)
44
C_RO1
C_RO1 from PLC(You need to set P27.00 to 1.)
45
C_RO2
C_RO2 from PLC (You need to set P27.00 to 1.)
46
C_RO3
C_RO3 from PLC (You need to set P27.00 to 1.)
47
C_RO4
C_RO4 from PLC (You need to set P27.00 to 1.)
48–63
Reserved variables
/
Related parameter list:
Function
code
Name
Detailed parameter description
Default
value
P06.00
HDO output type
0: Open collector high-speed pulse output
1: Open collector output
0
P06.01
Y output selection
0: Invalid
1: In running
2: In forward running
3: In reverse running
4: In jogging
5: Inverter fault
6: Frequency level detection FDT1
7: Frequency level detection FDT2
8: Frequency reached
9: Running in zero speed
10: Reach upper limit frequency
11: Reach lower limit frequency
12: Ready to run
13: In pre-exciting
14: Overload pre-alarm
15: Underload pre-alarm
16: Simple PLC stage completed
17: Simple PLC cycle completed
18: Reach set counting value
19: Reach designated counting value
20: External fault is valid
21: Reserved
22: Reach running time
23: Virtual terminal output of MODBUS
0
P06.02
HDO output selection
0
P06.03
Relay RO1 output
selection
1
P06.04
Relay RO2 output
selection
5