DRV-28 inverter
s Function parameter list
-170-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P08.04
Acceleration
time 4
Depend
on model
○
P08.05
Deceleration
time 4
Depend
on model
○
P08.06
Running
frequency of
jogging
This function code is used to define the reference
frequency of the inverter during jogging.
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
5.00Hz
○
P08.07
Acceleration time
of jogging
Jogging acceleration time is the time needed for the
inverter to accelerate from 0Hz to Max. output
frequency (P00.03).
Jogging deceleration time is the time needed from
decelerating from Max. output frequency (P00.03) to
0Hz.
Setting range: 0.0–3600.0s
Depend
on model
○
P08.08
Deceleration time
of jogging
○
P08.09 Jump frequency 1 When the set frequency is within the range of jump
frequency, the inverter will run at the boundary of
jump frequency.
The inverter can avoid mechanical resonance point
by setting the jump frequency, and three jump
frequency points can be set. If the jump frequency
points are set to 0, this function will be invalid.
Set frequency f
Time t
Jump
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
0.00Hz
○
P08.10
Jump frequency
amplitude 1
0.00Hz
○
P08.11 Jump frequency 2
0.00Hz
○
P08.12
Jump frequency
amplitude 2
0.00Hz
○
P08.13 Jump frequency 3
0.00Hz
○
P08.14
Jump frequency
amplitude 3
0.00Hz
○
P08.15
Amplitude of
wobbling
frequency
0.0–100.0% (relative to set frequency)
0.0%
○
P08.16
Amplitude of
jump frequency
0.0–50.0% (relative to amplitude of wobbling
frequency)
0.0%
○
P08.17
Rise time of
wobbling
0.1–3600.0s
5.0s
○