Maintenance and Troubleshooting 11-35
Note:
You must reactivate the monitor through a
direct (
serial
) connection before you can resume
wireless communications following SIM card
replacement.
26.
Establish wireless communication with the monitor to verify
communication.
27.
Recoil and secure the antenna cable to the cable tie mount
using a cable tie, if necessary. Refer to Installing the Antenna
in Chapter 3,
Communication
, for more information.
Replacing the Fuses in the Monitor
The
monitor contains a removable power regulator
secured to a special dome that resides inside the monitor enclosure
and is attached to the monitor top. If a regulator failure occurs, it
typically involves a bad fuse on the regulator board corresponding
to communications or sensors. The regulator board has
three
fuses,
indicated by three color-corresponding LED lights on top of the
monitor, (ADS p/n 508071, 508072, and 508073) that may be
replaced independently upon failure.
The 5-volt
blue
fuse corresponds to the sensors and can be blown
due to a shorted sensor. If this fuse is blown, the monitor cannot
detect the sensors. The 3.3-volt
yellow
fuse is associated with the
processor board. When blown, this fuse prevents the monitor from
logging data and performing successful communications. The red
(main input) fuse is related to the regulator board and rarely has
issues.
Refer to the
Troubleshooting
section beginning on page 11-44 to
identify whether a fuse may be the source of a particular problem
that has occurred within the
system and, if so, which
fuse may require replacement.
Note:
If the troubleshooting procedures indicate that a
sensor may have shorted
or
a sensor may have shorted and
the 5-volt (blue) fuse on the power regulator in the monitor
corresponding to the sensor may have blown,
do not
connect the potentially shorted sensor to the same monitor
Содержание 507165
Страница 20: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 27: ...Introduction 1 19 CS6 LRD Sensor Certificate of Conformity ...
Страница 29: ...Introduction 1 21 CSA Certificate of Compliance Page 1 of 7 ...
Страница 30: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 2 of 7 ...
Страница 31: ...Introduction 1 23 CSA Certificate of Compliance Page 3 of 7 ...
Страница 32: ...1 24 ADS TRITON Manual CSA Certificate of Compliance Page 4 of 7 ...
Страница 33: ...Introduction 1 25 CSA Certificate of Compliance Page 5 of 7 ...
Страница 34: ...1 26 ADS TRITON Manual CSA Certificate of Compliance Page 6 of 7 ...
Страница 35: ...Introduction 1 27 CSA Certificate of Compliance Page 7 of 7 ...
Страница 37: ...Introduction 1 29 Sample TRITON Declaration of Conformity Page 2 ...
Страница 53: ...System Overview 2 13 ExPAC XBUS ...
Страница 266: ...5 60 ADS TRITON Manual z Installing the Submersion Sensor z Measuring the physical offset ...
Страница 288: ...5 82 ADS TRITON Manual Topside Wall Mount Bracket Topside Sensor Bracket ...
Страница 292: ...5 86 ADS TRITON Manual Confirm Level Front to Back Installed ParaDepth ParaFlow Wall Mount Bracket ...
Страница 315: ...External Power 6 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 327: ...External Power 6 21 Wires exiting DC output terminal on power supply POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS ...
Страница 345: ...7 2 ADS TRITON Manual use of this installation guide or the installation of any ADS equipment ...
Страница 358: ...Inclinometer 8 3 ...
Страница 507: ...C 4 ADS TRITON Manual ...
Страница 535: ...Index In 19 wiring to the monitor 6 29 XIO device parameters 4 84 ...