External Power
6-23
the monitor top at which the ground wire from the ExPAC
terminates.
When using an ExPAC, you first must install two ground terminal
blocks next to the ExPAC and run a short ground wire from the
ExPAC to one of two ground terminal blocks adjacent to the
ExPAC. Then, you must run a ground wire from one of the ground
terminal blocks to the existing earth ground outside the applicable
enclosure
and
run another ground wire from the other ground
terminal block to the
monitor’s ground connection
facility.
The
10-gauge
ground wire that runs between a ground terminal
block and the monitor is included in an
external power grounding
kit
available through ADS (p/n 8000-0434-xxx). This kit is
required
for all external power applications. For the ground wire
that runs between a ground terminal block and the existing earth
ground, ADS recommends using at least a
12-gauge
ground wire
.
For applications that do not include the XIO or XBUS, you must
acquire
two
ground terminal blocks that can accommodate 18- to
10-gauge wires and obtain an
18-gauge
ground wire to run from the
ExPAC to a ground terminal block.
Install the ground wiring in the following way:
1.
(
applies only to applications without an XIO or XBUS
)
Perform the following steps to prepare the ExPAC before
running the two primary ground wires:
Mount two ground terminal blocks on the existing DIN
rail or other suitable structure to the right of the ExPAC.
Remember, you must use terminal blocks that can
accommodate 18- to 10-gauge ground wire.
Note:
If you are not mounting the ground terminal blocks
to a metal DIN rail, make sure they are mounted to a
structure or intersect in such a way that ensures that all the
ground wires attached to both terminal blocks share a
common electrical connection.
Содержание 507165
Страница 20: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 27: ...Introduction 1 19 CS6 LRD Sensor Certificate of Conformity ...
Страница 29: ...Introduction 1 21 CSA Certificate of Compliance Page 1 of 7 ...
Страница 30: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 2 of 7 ...
Страница 31: ...Introduction 1 23 CSA Certificate of Compliance Page 3 of 7 ...
Страница 32: ...1 24 ADS TRITON Manual CSA Certificate of Compliance Page 4 of 7 ...
Страница 33: ...Introduction 1 25 CSA Certificate of Compliance Page 5 of 7 ...
Страница 34: ...1 26 ADS TRITON Manual CSA Certificate of Compliance Page 6 of 7 ...
Страница 35: ...Introduction 1 27 CSA Certificate of Compliance Page 7 of 7 ...
Страница 37: ...Introduction 1 29 Sample TRITON Declaration of Conformity Page 2 ...
Страница 53: ...System Overview 2 13 ExPAC XBUS ...
Страница 266: ...5 60 ADS TRITON Manual z Installing the Submersion Sensor z Measuring the physical offset ...
Страница 288: ...5 82 ADS TRITON Manual Topside Wall Mount Bracket Topside Sensor Bracket ...
Страница 292: ...5 86 ADS TRITON Manual Confirm Level Front to Back Installed ParaDepth ParaFlow Wall Mount Bracket ...
Страница 315: ...External Power 6 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 327: ...External Power 6 21 Wires exiting DC output terminal on power supply POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS ...
Страница 345: ...7 2 ADS TRITON Manual use of this installation guide or the installation of any ADS equipment ...
Страница 358: ...Inclinometer 8 3 ...
Страница 507: ...C 4 ADS TRITON Manual ...
Страница 535: ...Index In 19 wiring to the monitor 6 29 XIO device parameters 4 84 ...