Analog and Digital I/O 9-9
signal wiring. Setup may involve penetrating existing
enclosures, running conduit, or sealing glands.
2.
Establish the range and engineering units representing 4 to
20mA for the analog output, and then configure the
Analog Output 1 (or 2) component of the XIO Device
through
Q
start
XML
with the analog output parameters that
indicate the values or measurements that correspond to the
analog signals within the 4-20mA range. Refer to
Chapter
4
,
Configuration and Activation
, for instructions on
supplying this information in
Q
start
XML
.
3.
Configure the device or instrument receiving the analog
signals with the range and engineering units corresponding
to the 4-20mA from the
TRITON
+.
4.
Connect the analog output wires (from the customer-
supplied cable) to the ADS XIO in the following way:
Note:
Make sure the power is turned off to the third-party
device and XIO.
Release the latches and open the clear, front door on
the XIO.
Run the wires up through the left cable gland on the
XIO into the enclosure. ADS recommends using 18-
gauge wiring. You may need to loosen the plastic nut
on the cable gland on the outside of the XIO to feed
the wires through.
Содержание 507165
Страница 20: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 27: ...Introduction 1 19 CS6 LRD Sensor Certificate of Conformity ...
Страница 29: ...Introduction 1 21 CSA Certificate of Compliance Page 1 of 7 ...
Страница 30: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 2 of 7 ...
Страница 31: ...Introduction 1 23 CSA Certificate of Compliance Page 3 of 7 ...
Страница 32: ...1 24 ADS TRITON Manual CSA Certificate of Compliance Page 4 of 7 ...
Страница 33: ...Introduction 1 25 CSA Certificate of Compliance Page 5 of 7 ...
Страница 34: ...1 26 ADS TRITON Manual CSA Certificate of Compliance Page 6 of 7 ...
Страница 35: ...Introduction 1 27 CSA Certificate of Compliance Page 7 of 7 ...
Страница 37: ...Introduction 1 29 Sample TRITON Declaration of Conformity Page 2 ...
Страница 53: ...System Overview 2 13 ExPAC XBUS ...
Страница 266: ...5 60 ADS TRITON Manual z Installing the Submersion Sensor z Measuring the physical offset ...
Страница 288: ...5 82 ADS TRITON Manual Topside Wall Mount Bracket Topside Sensor Bracket ...
Страница 292: ...5 86 ADS TRITON Manual Confirm Level Front to Back Installed ParaDepth ParaFlow Wall Mount Bracket ...
Страница 315: ...External Power 6 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 327: ...External Power 6 21 Wires exiting DC output terminal on power supply POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS ...
Страница 345: ...7 2 ADS TRITON Manual use of this installation guide or the installation of any ADS equipment ...
Страница 358: ...Inclinometer 8 3 ...
Страница 507: ...C 4 ADS TRITON Manual ...
Страница 535: ...Index In 19 wiring to the monitor 6 29 XIO device parameters 4 84 ...