Analog and Digital I/O 9-13
Digital Inputs
The
(with an ADS XIO) supports the monitoring of up
to two digital inputs from third-party devices, such as switches or
alarms (relays). To properly configure the monitor to process the
signals received from these devices, you must configure each input
as active through the ADS
Q
start
XML
software.
Connecting a Third-Party Device to a Digital
Input on the XIO
Perform the following procedure to connect each third-party device
(up to two) to a digital input terminal on the ADS XIO:
Note:
Make sure external power is available,
but not
turned on
, to the monitor before connecting the signal
wiring. If it is not available, you cannot complete testing,
which may require return visits by the owner
representative and/or electrician or instrument technician
for wiring problems.
1.
Configure the
Digital Input 1
(or
2
) component of the
XIO
Device
through
Q
start
XML
to indicate the digital input is active
and whether you want the monitor to store the data received.
Refer to
Chapter 4
,
Configuration and Activation
, for
instructions on supplying these settings in
Q
start
XML
.
2.
Connect the digital input wires to the ADS XIO in the
following way:
Note:
Make sure the power is turned off to the third-party
device and XIO.
Release the latches and open the clear, front door on the
XIO.
Содержание 507165
Страница 20: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 27: ...Introduction 1 19 CS6 LRD Sensor Certificate of Conformity ...
Страница 29: ...Introduction 1 21 CSA Certificate of Compliance Page 1 of 7 ...
Страница 30: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 2 of 7 ...
Страница 31: ...Introduction 1 23 CSA Certificate of Compliance Page 3 of 7 ...
Страница 32: ...1 24 ADS TRITON Manual CSA Certificate of Compliance Page 4 of 7 ...
Страница 33: ...Introduction 1 25 CSA Certificate of Compliance Page 5 of 7 ...
Страница 34: ...1 26 ADS TRITON Manual CSA Certificate of Compliance Page 6 of 7 ...
Страница 35: ...Introduction 1 27 CSA Certificate of Compliance Page 7 of 7 ...
Страница 37: ...Introduction 1 29 Sample TRITON Declaration of Conformity Page 2 ...
Страница 53: ...System Overview 2 13 ExPAC XBUS ...
Страница 266: ...5 60 ADS TRITON Manual z Installing the Submersion Sensor z Measuring the physical offset ...
Страница 288: ...5 82 ADS TRITON Manual Topside Wall Mount Bracket Topside Sensor Bracket ...
Страница 292: ...5 86 ADS TRITON Manual Confirm Level Front to Back Installed ParaDepth ParaFlow Wall Mount Bracket ...
Страница 315: ...External Power 6 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 327: ...External Power 6 21 Wires exiting DC output terminal on power supply POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS ...
Страница 345: ...7 2 ADS TRITON Manual use of this installation guide or the installation of any ADS equipment ...
Страница 358: ...Inclinometer 8 3 ...
Страница 507: ...C 4 ADS TRITON Manual ...
Страница 535: ...Index In 19 wiring to the monitor 6 29 XIO device parameters 4 84 ...