H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
LCD Display
Description
Page
78
External torque
reference polarity
inversion
Tref Sign Change
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Open: Forward torque reference.
Closed: Reverse polarity.
7E
Forward/reverse
detection
(V/f Control with Simple
PG feedback)
PG Rotate Rev
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f w PG
Direction of rotation detection (for V/f with Simple PG Feedback)
7F
PID Bi-Directional
Enable
PID BiDir Enable
All Modes
Reserved.
–
90 to 97 DriveWorksEZ
digital inputs 1 to 8
–
All Modes
Reserved for DWEZ input functions
9F
DriveWorksEZ disabled DWEZ Disable
All Modes
Open: DWEZ enabled
Closed: DWEZ disabled
u
H2: Multi-Function Digital Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H2-01
(040B)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
All Modes
Refer to H2 Multi-Function Digital Output Settings on pages
for descriptions of setting values.
Default: 0
Range: 0 to 192
H2-02
(040C)
Terminal M3-M4
function selection
(relay)
P1/PC Func Sel
Default: 1
Range: 0 to 192
H2-03
(040D)
Terminal M5-M6
function selection
(relay)
P2/PC Func Sel
Default: 2
Range: 0 to 192
H2-06
(0437)
Power Consumption
Output Unit Selection
Pwr Mon Unit Sel
All Modes
Sets the units for the output signal when Power Consumption
Pulse Output or Regenerated Power Pulse Output are selected
as the digital output (H2-01, H2-02, or H2-03 = 39 or 3A).
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 1
Range: 0 to 4
H2-07
(0B3A)
MEMOBUS Register 1
Address Select
MFDO Regs1 Addr
All Modes
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 62 and 162.
Default: 1
Range: 1 to
1FFFH
H2-08
(0B3B)
MEMOBUS Register 1
Bit Select
MFDO Regs1 Bit
All Modes
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 62 and 162.
Default: 0
Range: 0 to
FFFFH
H2-09
(0B3C)
MEMOBUS Register 2
Address Select
MFDO Regs2 Addr
All Modes
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 63 and 163.
Default: 1
Range: 1 to
1FFFH
H2-10
(0B3D)
MEMOBUS Register 2
Bit Select
MFDO Regs2 Bit
All Modes
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 63 and 163.
Default: 0
Range: 0 to
FFFFH
<1> Available in drive software versions PRG: 1015 and later.
B.9 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
539
B
Parameter List