No.
Name
Setting Range
Resolution
Control Modes (A1-02)
OLV/PM (5)
AOLV/PM (6)
CLV/PM (7)
C4-02
Torque Compensation Primary Delay Time
0 to 10000
1 ms
100
–
–
C5-01
ASR Proportional Gain 1
0.00 to 300.00
0.01
–
10.00
20.00
C5-02
ASR Integral Time 1
0.000 to 10.000
0.001 s
–
0.500
0.500
C5-03
ASR Proportional Gain 2
0.00 to 300.00
0.01
–
10.00
20.00
C5-04
ASR Integral Time 2
0.000 to 10.000
0.001 s
–
0.500
0.500
C5-06
ASR Primary Delay Time Constant
0.000 to 0.500
0.001 s
–
0.016
0.004
C5-07
ASR Gain Switching Frequency
0.0 to 400.0 Hz
0.1
–
0.0%
0.0%
C6-02
Carrier Frequency Selection
0 to 4; F
–
1
1
1
d3-01
Jump Frequency 1
0.0 to 400.0 Hz
0.1
0.0 Hz
0.0%
0.0%
d3-02
Jump Frequency 2
0.0 to 400.0 Hz
0.1
0.0 Hz
0.0%
0.0%
d3-03
Jump Frequency 3
0.0 to 400.0 Hz
0.1
0.0 Hz
0.0%
0.0%
d3-04
Jump Frequency Width
0.0 to 20.0
0.1
1.0 Hz
1.0%
1.0%
d5-02
Torque Reference Delay Time
0 to 1000
1 ms
–
–
–
E1-04
Maximum Output Frequency
40.0 to 400.0
0.1 Hz
E1-05
Maximum Voltage
0.0 to 377.1
0.1 V
E1-06
Base Frequency
0.0 to 400.0
0.1 Hz
E1-07
Middle Output Frequency
0.0 to 400.0
0.1 Hz
–
–
–
E1-08
Middle Output Frequency Voltage
0.0 to 377.1
0.1 V
–
–
–
E1-09
Minimum Output Frequency
0.0 to 400.0
0.1 Hz
0.0
E1-10
Minimum Output Frequency Voltage
0.0 to 377.1
0.1 V
–
–
–
F1-01
PG 1 Pulses Per Revolution
0 to 60000
1 ppr
–
–
1024
F1-05
PG 1 Rotation Selection
0, 1
–
–
–
1
F1-09
Overspeed Detection Delay Time
0.0 to 2.0
0.1 s
–
0.0
0.0
L1-01
Motor Overload Protection Selection
0 to 6
–
4
4
5
L3-36
Vibration Suppression Gain during
Acceleration (with Current Limit)
0.0 to 100.0
–
–
–
–
L3-41
Vibration Suppression Gain during
Deceleration (with Current Limit)
0.0 to 100.0
–
–
–
–
L4-01
Speed Agree Detection Level
0.0 to 400.0 Hz
0.1
0.0 Hz
0.0%
0.0%
L4-02
Speed Agree Detection Width
0.0 to 20.0
0.1 Hz
2.0 Hz
4.0%
L4-03
Speed Agree Detection Level (+/-)
0.0 to 400.0 Hz
0.1
0.0 Hz
0.0%
0.0%
L4-04
Speed Agree Detection Width (+/-)
0.0 to 20.0
0.1 Hz
2.0 Hz
4.0%
L8-18
Software Current Limit Selection
0, 1
–
0
0
0
L8-38
Carrier Frequency Reduction Selection
0 to 2
–
0
–
0
L8-40
Carrier Frequency Reduction Off Delay
Time
0.00 to 2.00
0.01 s
0.00
–
0.00
o1-03
Digital Operator Display Selection
0 to 3
–
0
1
1
o1-04
V/f Pattern Display Unit
0, 1
–
–
1
1
<1> Value calculated as a percentage of the maximum output frequency.
<2> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 100.0%) instead of in Hz.
<3> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 40.0%) instead of in Hz.
<4> Default setting is dependent on parameter E5-01, Motor Code Selection.
<5> Values shown are specific to 200 V class drives. Double the values for 400 V class drives.
<6> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (-100.0 to 100.0%) instead of in Hz.
B.16 Control Mode Dependent Parameter Default Values
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
585
B
Parameter List