Auto-Tuning Operation Example
The following example demonstrates Rotational Auto-Tuning when using OLV (A1-02 = 2) and CLV (A1-02 = 3).
n
Selecting the Type of Auto-Tuning
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
2.
Press
or
until the Auto-Tuning display appears.
HELP
- MODE -
PRG
Auto-Tuning
DATA
AUTO
FWD
3.
Press
to display T1-01 and the current setting 0 (Rotational Auto-Tuning).
- A.TUNE -
T1-
01
= 0
*
0
*
Standard Tuning
PRG
Tuning Mode Sel
Rdy
ESC
FWD
DATA
4.
Press
. The T1-01 setting flashes and can now be changed.
- A.TUNE -
T1-01=
0
*
0
*
Standard Tuning
PRG
Tuning Mode Sel
Rdy
FWD
“0”
5.
The setting is already 0 (Rotational Auto-Tuning). Do not change the setting.
Press
.
Entry Accepted
6.
The display automatically returns to the display shown in Step 3.
- A.TUNE -
T1-
01
= 0
*
0
*
Standard Tuning
PRG
Tuning Mode Sel
Rdy
ESC
FWD
DATA
n
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note:
These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.
Step
Display/Result
1.
Press
to access the motor output power parameter T1-02.
The value set for E2-11 prior to turning on the power is displayed for T1-02.
- A.TUNE -
T1-
02
= 0.75kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
Rdy
ESC
FWD
DATA
“0.75kW”
2.
The setting value of T1-02 flashes when
is pressed.
The setting can be changed.
- A.TUNE -
T1-02=
0
00.75kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
Rdy
FWD
“0.75kW”
3.
Press
F1
left
,
F2
right
,
,
, and
to enter the motor power nameplate data in
kW.
- A.TUNE -
T1-02= 000.4
0
kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
Rdy
FWD
“0.75kW”
4.
Press
to save the setting.
Entry Accepted